基于故障信息系统的电网智能决策系统的研究

Research of Power Grid Intelligent Decision System Based on Relay Protection and Fault Information System

【作者】 徐斌

【导师】 田小建;

【作者基本信息】 吉林大学 , 电路与系统, 2008, 硕士

【摘要】 近年来,伴随国民经济的高速增长和社会快速进步,电力作为国家支柱产业迅速发展壮大;数字化、信息化技术在电网中大量应用,使电网发展呈现出规模化、智能化的特点。继电保护作为保障电网安全稳定运行的第一道防线,担负保障电网和电力设备安全的重要职责。故障录波器是电力系统记录动态过程重要的精密设备,为评价继电保护动作行为及分析设备故障性质和原因提供了重要依据。故障信息系统实现了将保护和故障录波器以及开关动作信息快速传送至调度端,为科学分析故障各种信息,实现对电网故障智能诊断和辅助决策提供了支撑平台,吉林省故障信信息管理系统已经投入运行,实现了故障信息的自动采集和Web发布。通过信号分析和处理技术的应用,实现保护动作行为的子站端分析,为故障诊断提供依据。通过专家系统和信息处理技术的综合运用,实现主站端智能诊断和辅助决策,大大提高调度人员事故处理的快速性和准确性,为保证电网的安全稳定运行发挥至关重要作用。

【Abstract】 In recent years, following the high speed growth of national economy and the social fast advancement, the electric power has been developed quickly as pillar industry of the country. Because the digitization and information technology are widely applied, the electric network development shows the scale and intellectualized characteristics. On the one hand, the function of resource optimizing configuration is improved by the large electrical network interconnection, on the other hand the affecting scope of electric network fault is expanded. The national economy and social stability are influenced very much by the fault. Since the 1960s, many cataclysm power system faults have taken place around the world, caused large economic losses and huge social impact.The fault settlement of electric power system is the extremely complex real-time decision-making process. There are many factors including many uncertainty ones to affect the correct process. Formerly the local decision mainly depends on dispatcher’s experience. When the electrical network breaks down, the dispatcher must rapidly and accurately diagnose the fault, give out the corresponding processing measure, restore the normal operation in time, according to the fault information. It is the precondition and foundation that the fault is rapidly and correctly diagnosed. But the modern electrical network is more and more complex; it is very difficult to satisfy the requirements of fault settlement that only depend on the dispatcher’s theory knowledge and experience.As the first defense line guaranteeing the electrical network safe and stable run, the microcomputer relay protection takes on the important responsibility to ensure the electrical network and the electric equipment safe. The alternate current and voltage information are turned into the low level digital signal by the A/D transformation. Then the CPUs in the protection device carry out a series of functions according to the protection operating principle, such as data processing, value operation and logical judgment and so on, provide the hard contact information reflecting protection basic survey and the data of protection action.The fault recorder is the important precision equipment to record the electric power system dynamic process. It gathers the current, voltage information and so on, simultaneously cuts in the circuit breaker phase splitting trip information, protection information and pilot protection channel information. The fault recorder has provided the important reference for evaluating relay protection action and analyzing the nature and reason of equipment fault.The fault information management system has established based on the interconnection of microcomputer relay protection and digital fault recorder. It has realized that the protection, fault recorder and switch act information are quickly sent to the dispatch. And it has provided a supporting platform for the scientific analysis of all kinds of fault information, realized fault intelligent diagnosis and the assistant decision-making.The relay protection fault information management system design of Jilin Province 220kV electric network adopts tri-level frame including master station, centralized control station and substation, uses ATM as the data transmission channel. The master station is located at Jilin dispatch center. The centralized control stations are set up at Siping, Tonghua , Yanbian, Changchun, Jilin, Liaoyuan, Baicheng and Baishan local dispatch. The substations are situated at 54 220kV substations managed by Jilin Province dispatch center.The communication system is made up by two ATM virtual special net, each 220kV substation has two 10M Ethernet interfaces, each centralized control station has two 10M Ethernet interfaces, the master station has four l00M Ethernet interfaces, separately composing the protection and fault record net, they are isolated each other, The separate transmission between the protection and fault record information has been realized. Two kinds of information converge through exchange in master station at last. The information of the relay protection action, run, setting value, operating characteristic and channel, the circuit breaker action, the fault recorder, and so on, which concern the electrical network safe operation in substation, are transmitted to the master station by the information transmission equipments. The comprehensive analysis and use to the substation information has been realized in the master station through the information preservation and treatment.At the information collection and management function, the categoricalness of raw information acquisition and the selectivity of report information are emphasized in the part of substation. Using the ability which wavelet transform can detect the fault signal irregularity, the data of the fault recorder has been analyzed. It has realized the fault time detection, the identification of line fault nature and the protection action, the selective upload information.The fault diagnosis is the most important function in the electric network fault information system. It analyzes the various action signals of circuit breakers and protection devices, the electrical quantities measurement of voltage, current and so on in the substation. According to the open circuit breaker and the action logic of protection, the position and type of the fault can be concluded. In order to enhance the reliability and accuracy of the electric network fault information management system and deal with a various of electric network fault correctly, a kind of layering fault information processing and diagnosis method is proposed and has been realized in the system combinating the facts of Jilin electric network.To the online fault diagnosis of the complex electric network fault, the protection and circuit breaker don’t correctly act at the same time, the paper presented that apply the information theory to deal with the fault messages. It is the information movement process that the protection and circuit breaker act when the electric power system breaks down. An essence of information movement is uncertainty, lying lots of random information. Therefore, the intelligent electric network fault diagnosis based on information theory can be a good reaction of the uncertainty between fault and indication, improve the reality and accuracy of fault diagnosis. The power system online fault diagnosis methods based on information theory, can give the probability distribution of many possible solutions in the decision result. The master station intelligent diagnosis and aid decision-making has been realized by the way of synthesis application of the expert systems and information processing technology. And the rapidity and accuracy which the dispatchers deal with the fault has been greatly enhanced. This system plays a vital role to ensure the electric network safe and stable operation.

  • 【网络出版投稿人】 吉林大学
  • 【网络出版年期】2008年 11期
  • 【分类号】TM77;TP277
  • 【被引频次】1
  • 【下载频次】282
节点文献中: