【摘要】 针对隔河岩电厂发生的线路保护及发变组保护动作的故障,对该保护动作信号情况及对主变压器的影响进行了分别计算分析,证明了该厂相关保护动作是正确的。
【Abstract】 In view of failure in protective action of line and generator-transformer unit in Geheyan Hydropower Plant,the calculating analyses of protective action signal and its influence on the main transformer are made separately.It shows that the relative protective action is correct.
【关键词】 零序电流保护;
失灵保护;
单相接地故障;
【Key words】 zerosequence current; failure protection; singlephase grounding failure;