节点文献

高邮地震台地电阻率观测精度干扰原因分析及排除方法

An analysis of the reason for a disturbance in the earth resistivity observations at Gaoyou Seismic Station and the method for its elimination

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 王福才赵卫红蒋延林张骞吴荣兴

【Author】 WANG Fucai, ZHAO Weihong, JIANG Yanlin,ZHANG Qian, WU Rongxing(Gaoyou Seismic Station, Gaoyou 225600, China)

【机构】 高邮地震台高邮地震台 江苏高邮225600江苏高邮225600江苏高邮225600

【摘要】 对高邮台地电NS向ρs的观测精度在2002 07 24雷雨后出现降低的现象进行了分析排查,发现是一交流接触器在遭雷击时烧坏,导致交流电三相中的一相对地漏电,与变压器中的零线形成回路所致。从而排除了配电房漏电的干扰,保证了观测资料的质量。

【Abstract】 Comprehensive analyses and examinations are made of the reason for the reduction of the accuracy of the ρs observations on NS component at the Gaoyou Seismic Station after a thunder shower on July 24,2002. It is found that an a.c. contactor was burned down, leading to the leakage of electricity of one of the three phases of the alternate current to the earth and a loop was formed with the zero line in the transformer. Then, the disturbance was eliminated and the quality of observational data is ensured.

  • 【文献出处】 地震学刊 ,Journal of Seismology , 编辑部邮箱 ,2002年04期
  • 【分类号】P315.6
  • 【被引频次】1
  • 【下载频次】22
节点文献中: 

本文链接的文献网络图示:

本文的引文网络