节点文献

底层框架-抗震墙砌体房屋强震破坏模式及影响因素分析

Analysis on failure mode of masonry buildings with frame and seismic-wall in first story under strong earthquakes and its influencing factors

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 韩军韩夏李英民冯远吴勇

【Author】 HAN Jun;HAN Xia;LI Yingmin;FENG Yuan;WU Yong;College of Civil Engineering,Chongqing University;Key Laboratory of New Technology for Construction of Cities in Mountain Area,Ministry of Education;China Southwest Architectural Design and Research Institute Co. ,Ltd.;

【机构】 重庆大学土木工程学院山地城镇建设与新技术教育部重点实验室中国建筑西南设计研究院有限公司

【摘要】 规范对底层框架-抗震墙砌体房屋在强震中引导的破坏模式不够明确,抗整体倒塌性能不易控制。基于震害现象总结了底框结构的典型破坏模式,分析了影响破坏模式的主要因素,探讨了底框结构的合理破坏模式。通过算例分析考察了抗侧刚度比和屈强比对底框房屋结构的抗震性能及破坏模式的影响规律。结果表明:强震宜引导底框层作为薄弱部位耗能;刚度比和屈强比是影响底框房屋破坏模式的主要因素,刚度比越大,屈强比越小,底框层破坏程度越严重,上部楼层破坏程度越轻;7度区宜控制刚度比在1.25~2.0之间,屈强比在0.6~0.8之间,当刚度比较小时可适当减小屈强比,刚度比较大时可适当增大屈强比。

【Abstract】 The expected failure modes of masonry structures with frame-shear wall at the bottom are not clear enough in Chinese seismic design code. And the integer collapse resistance capacity is not easy to control. A summary of the typical failure modes was proposed according to earthquake damages,and the influencing factors of failure mode were analyzed. The expected failure modes are discussed. The influence rules of the story lateral stiffness ratio( i. e. the ratio of the lateral stiffness of the second floor to that of the first floor) and the story shear strength ratio( i. e. the ratio of the shear strength of the first floor to that of the second floor) on the failure modes and seismic performance of masonry structures with frame-shear wall at the bottom are studied by analyzing calculation examples. The results show that the first story is suitable to be guided as weak part to dissipate energy under strong earthquakes. The story lateral stiffness ratio and the story shear strength ratio are the main influencing factors on the failure modes. The greater the story lateral stiffness ratio or smaller the story shear strength ratio is,the more seriously damage of the lower frame-shear wall,and the less damage of the upper masonry structure will occur. The story lateral stiffness ratio should be control in the range of 1. 25 to 2. 00 and the story shear strength ratio should be control in the range of 0. 6 to 0. 9 in seismic zone of intensity 7. When the story lateral stiffness ratio is low,thestory shear strength ratio could be decreased. When the story lateral stiffness ratio is high,the story shear strength ratio could be increased.

【基金】 国家自然科学基金项目(51108486);重庆市建设科技计划项目(2011-2-87)
  • 【文献出处】 地震工程与工程振动 ,Earthquake Engineering and Engineering Dynamics , 编辑部邮箱 ,2014年S1期
  • 【分类号】TU352.11;TU312.3
  • 【被引频次】4
  • 【下载频次】99
节点文献中: 

本文链接的文献网络图示:

本文的引文网络