节点文献

酒店多能互补空调系统运行分析

Operating analysis of multi-energy complementary air conditioning system of a hotel

  • 推荐 CAJ下载
  • PDF下载
  • 不支持迅雷等下载工具,请取消加速工具后下载。

【作者】 肖芳斌潘李奎叶财发胡金泉郭广辉

【Author】 Xiao Fangbin;Pan Likui;Ye Caifa;Hu Jinquan;Guo Guanghui;Shenzhen McQuay Air Conditioning Co., Ltd.;Zhengzhou Yixing Air Conditioning Technology Service Co., Ltd.;

【机构】 深圳麦克维尔空调有限公司郑州亿兴空调技术服务有限公司

【摘要】 结合应用场所的实际冷热负荷和热水需求情况,采用复合蒸发冷凝热泵机组、低温强热空气源热泵机组和热回收空气源热泵机组,进行“精准适配”的制冷、制热和制热水设计。以郑州某四星级酒店为例,介绍了这3种空调的原理、计算模型、节能率和运行费用。相比常规的空气源热泵机组和燃气锅炉的制冷、制热、制热水方式,该方案整体节能24.5%。并利用机组实际运行数据验证了该计算模型的准确性。

【Abstract】 Combined with the actual cooling and heating load and hot water demand of the application site, the compound evaporative condensation air-source heat pump units, low temperature strong hot air-source heat pump units and heat recover air-source heat pump units are adopted for the accurate adaptation design for refrigeration, heating and hot water. Taking a four-star hotel in Zhengzhou as an example, this paper presents the principle, calculation model, energy saving rate and operation cost of these three kinds of air conditioning units. Compared with conventional air-source heat pumps and gas boilers, the energy saving rate of this case can rise by 24.5%. The accuracy of the calculation model is verified by using the actual operation data of the units.

  • 【文献出处】 暖通空调 ,Heating Ventilating & Air Conditioning , 编辑部邮箱 ,2022年05期
  • 【分类号】TU831.3
  • 【网络出版时间】2022-04-25 14:45:00
  • 【下载频次】108
节点文献中: 

本文链接的文献网络图示:

本文的引文网络